Quote of the Day
Life isn't about finding yourself. Life is about creating yourself.
— George Bernard Shaw:"
Introduction
I deal with a lot of battery issues. Our products generally ship with an Uninterruptible Power Supply (UPS) that contains a 7.2 A-hr Sealed Lead-Acid (SLA) battery (Figure 1). I occasionally hear customers say that we shipped them bad batteries. Since we charge the batteries just before shipment, I know the batteries left our facility functional and with a full charge. In every single case, the customer had not properly handled the batteries -- the batteries had become fully discharged because they had been stored for too long between charging cycles. A discharged lead-acid battery will eventually become sulfated -- a state where the battery plates are coated with a crystalline layer of lead sulfate and lead oxide. Some people refer to this layer as a "varnish" because sulfated plates look like they are coated with wood varnish. A sulfated battery usually is only good for recycling. See the Appendix of this post for a reference on the topic.
During a normal discharge cycle, lead-acid batteries form a layer of amorphous lead sulfate on their plates. Charging converts the amorphous form of lead sulfate back to lead. Unfortunately, when a discharged battery is stored for a long period of time (usually weeks or months), the amorphous lead sulfate changes into a crystalline form that cannot be converted back to lead through normal charging. This paper has great photos that actually show you the crystals that form.
When I first started this job, I would often go to the deployment sites to investigate reports of customers receiving dead batteries. My first customer visit was pretty typical. The customer was angry that all of his batteries were dead. I started my investigation by asking him how he handled his batteries. He told me that his UPS units were stored in warehouse prior to being installed. I asked him if I could visit the warehouse and he proceeded to take me to a large barn. The UPS units and their batteries were stored in the loft of the barn at a temperature of about 50°C (122 °F). They typically sat in the warehouse for three to four months before being deployed. The batteries were dying during that storage period. I told my customer that the batteries were not being stored according to the vendor's battery storage requirements. He said that no one ever told him what the battery handling requirements were and I needed to pay to replace every one of his failing batteries (including service call). I then reached into a UPS box and pulled out the battery handling specification that ships with every UPS. He seemed pretty sheepish after seeing that he had received thousands of battery handling instruction sheets. He had never actually looked in the boxes.
At room temperature, batteries can sit for months without a problem. However, batteries at high temperature can fail in a very short period of time. Let's examine this acceleration closer.
Background
Few batteries die a natural death -- most batteries are murdered. They are murdered by owners that charge them improperly, cycle them too deeply, let them sit discharged for too long, or store them at too high a temperature. Since our UPS units have built-in controllers and the units are rarely deeply discharged, the primary battery killer is heat.
Batteries are electrochemical machines. Chemical reactions govern how they work and chemical reactions govern how they fail. Chemical reactions exist within a battery that cause them to discharge while just sitting in storage. Other chemical reactions cause them to form crystalline lead sulfate. Both of these reactions are accelerated by temperature according to the Arrhenius equation, which I state in Equation 1.
Eq. 1 |
where
- k is the rate of the chemical reaction
- Ea is the activation energy.
- R is the R is the universal gas constant.
- T is the absolute temperature in °K.
- A is a constant.
Equation 1 tells us that increasing temperature produces an exponential increase in reaction rate. Let's examine how this reaction rate affects a battery that appears to just be sitting there -- it actually is experiencing an internal chemical reaction that is discharging the battery. I also want to examine a common rule of thumb for electrical engineers.
A battery at a temperature of T+10 °C self-discharges twice as fast as the same battery at a temperature of T.
Is this rule true? If it is true, the customer that I mentioned earlier who stored his batteries at 50 °C would see his batteries discharged in his warehouse within about two and half months. At that point, the sulphation process begins. His batteries were dying right before his eyes.
Analysis
Empirical Battery Discharge Data
All battery vendors publish self-discharge data for their products. Each battery vendor's products have different self-discharge rates because the rates are a function of how the plates are constructed (i.e. different lead alloys). Figure 2 shows a particularly well done self-discharge chart.
Discussion
I am not an electrochemist and I will not discuss all the details of Equation 1, but we can learn some things from a qualitative examination of Figure 1.
- A lead-acid battery self-discharges over time.
- The chart shows that you do not want to let a battery discharge below 60% of its full capacity.
- A lead-acid battery can be stored for about a year at room temperature before it needs a recharge.
- At high temperature (i.e. >40°C), a battery self-discharges much more rapidly than at room temperature (~22 °C).
It is amazing how many batteries I have seen destroyed by high temperature. At one deployment site, I saw that the customer had over 900 batteries reported as failures. Every failed battery had been stored improperly and then installed in a private residence when fiber service was installed at that home. The UPS did a battery load test every ten days, so the battery would be reported as failed 10 days after it was installed, which means a technician had to physically go out to a person's home and replace the failed battery (often with another failed battery). This went on for a year.
I would not want to explain to my boss that I screwed up by not following the directions included with every battery. Replacing a battery is not cheap, and paying for a service call to install the battery is not cheap either. There were many tens thousands of dollars worth of avoidable problems at this one customer site alone.
Rule of Thumb Accuracy
Assume that we want to ensure that our batteries never drop below 60% of full charge. In Figure 1, we see that as the battery temperature raises from 30 °C to 40 °C, the self-discharge time reduces from 8 months to about 5 months, which is less than half. We also see that as the battery temperature raises from 25 °C to 40 °C, the self-discharge time reduces from 13 months to about 5 months, which is more than half. So the actual doubling (or halving) temperature difference is between 10 °C and 15 °C. So the rule of thumb appears to provide a pessimistic answer in this case, which is okay for a rule of thumb.
Note that the exponential function and the rule of thumb are only related approximately. The derivation in Figure 3 shows that the rule of thumb is only true for a limited range of values. However, the range of values is reasonable with respect to lead-acid batteries.
The derivation shows that the 1/10.25 K is the proportionality "constant" for temperatures near 22 °C (room temperature) --the slow variation of the logarithm function helps us here. This means that the reaction rate roughly doubles for a 10.25 °C increase in temperature. The "constant" varies a bit across the temperature range of a battery. Figure 4 shows this variation. For a rule of thumb, it is not bad.
Conclusion
As summer nears, I will again receive calls from people about dead batteries. I hope I can provide guidance to people on how to avoid a costly and avoidable error.
Appendix
Activation Energy
Figure 5 is an excerpt from a battery reference ("Valve-Regulated Lead-Acid Batteries" by David Anthony and James Rand) that provides a value for the activation energy for the self-discharge reaction in a lead-acid battery.
Discussion of the Crystalline Layer
Figure 6 is an excerpt from page 16 of "Valve-Regulated Lead-Acid Batteries" by David Anthony and James Rand that discusses the formation of an insulating layer.
Pingback: Lead Acid Battery Life Math | Math Encounters Blog
Pingback: Battery Failure Rates and Continuously-Compounded Interest | Math Encounters Blog
Pingback: Compact Thermal Models for Electrical Components | Math Encounters Blog
I worked in the electronic surveillance industry for about 12 years as an electronics engineer, and I was astonished at the good condition of the 12volt lead-acid jelly batteries in very old (15 to 20 years) bell boxes that had been discarded for other reasons. WHY?
I concluded that the method of holding the lead-acid bettery at 13.8volt ALL THE TIME as a float charge by a small mains power unit was the reason. SO...
1) Keep your lead-acid cool.
2) Keep it at float charge all the time.
3) Your lead acid then will likely outlast the service life of the device.
Very sound advice. I too have had some batteries that have lasted very long in float applications and under the same operating conditions that you list.
mathscinotes
I used to work for a medical device company and we shipped 100's of thousands of SLA batteries in our infusion pump products every year. I did quite a bit of work on optimizing charge profiles to achieve good cycle life, avoid thermal runaway etc. etc.
Having access to lots of used batteries from general service returns I used a lot of batteries at home and there the usage pattern was mostly float (alarm system,door bell,garden water timer,computer backup etc) rather than cycle use. This mirrors Fred's usage pattern. I had batteries last over 20years (both starved (Gates/enersys/panasonic) and gelled cells sonneschein)), however there are some issues that arise in long term float use. The corrosion products and oxidation products cause the plates to grow (happens for very large # cycles too). This can cause the plates to short sometimes at the ends as they can grow into the connecting tabs. This is manufacturer dependent. It used to happen in early versions of cylindrical Gates products until they increased the spacing. In the Gates/enersys cylindrical products the thickening of the plates actually helps keep the active material in good contact with the grid as they age. However,in prismatic cells (eg Sonnenschein, Panasonic) the thickening of plates often causes the cases to bulge very substantially. Often the user can then no longer remove the battery from the product because the designers did not make allowance for this expansion. Internal cell shorts can cause similar bulging. It really helps to temperature compensate the float voltage and keep it lower than needed for cycle use. This keeps the integrated float current over the long term down, which is what drives plate growth. Temperature compensated smart charge algorithms to deal with mixed cycle/float usage are even better.
Mark your quote from "Valve-Regulated Lead-Acid Batteries" above needs to be tempered a bit, since it is less applicable to batteries having PbSn grids.
It was discovered by the Japanese first, that alloying the grids with Tin greatly reduced those problems. Initially they used rather small % of Tin to avoid additional corrosion of having an alloy. However, they discovered a larger (something like 2-4% ?) of tin worked even better, so even Gates/Enersys which had always advertised the feature of its "pure lead grid" cells then started to advertise their "pure lead-tin grids" ! The Gates/enersys grids are stamped from sheet while the Panasonic prismatic grids are cast. The Sn alloying makes the stamping and rolling of the Enersys grids more difficult as the Sn alloy is much harder, so the Panasonic grids likely use a higher % Sn. The improvement in grid-active material interface far outweighs any possible increased grid corrosion of the alloy
A general issue with cells and batteries is how the cells are "formed" and the first few cycles where forming is still taking place. As a result Bell labs showed many years ago that the first few cycles could have a large impact on battery life. It is very costly for battery vendors to cycle their batteries, so as shipped the cells are not properly formed unless you pay extra for more cycles or cycle them yourself before product is shipped.
Starved electrolyte cells are often "pot formed" in their cases, rather than tank formed like car batteries and pot forming is a more variable and costly process.
With controlled "formation" cycling the battery capacity usually rises significantly in the first 20 or so cycles, plateaus and then very slowly declines however the decline depends a lot on how smart your charging algorithms and your usage/abuse patterns. For example with better charge algorithms for cyclic use the decline can be very slow. If the first few cycles are abusive this can have a big impact on life. Anecdotally it seems that before complete formation, new semi-formed cells are more prone to thermal runaway. In the case of starved electrolyte cells the exact amount of electrolyte wetting the glass mat and how it is dispersed is critical, so unless the vendor has good process control you can get bad lots of batteries. In excess electrolyte gelled cells there are just different issues.
Process control seems a general problem, given most vendors keep moving there manufacturing to more and more remote places to cut labor costs and avoid anti-pollution laws!
Pingback: IoT Use Case - Battery Powered Device - OnTimeFeed